home *** CD-ROM | disk | FTP | other *** search
/ Spec Disk 1998 Spring 4.0 / Spec Disk 1998 Spring 4.0.iso / generic / 16132cep.gen < prev    next >
Text File  |  1998-06-10  |  6KB  |  166 lines

  1.     SECTION 16132
  2.  
  3.     SURFACE NONMETALLIC RACEWAYS
  4. NOTE ** This section is based on products offered by Carlon, at the following address:
  5. NOTE **      25701 Science Park Drive
  6. NOTE **      Cleveland, Ohio  44122
  7. NOTE **      Tel:  (800) 321-1970 (outside of Ohio)
  8. NOTE **            (216) 464-3400 (within Ohio)
  9. NOTE **      TDD:  (216) 831-5918
  10. NOTE **      Fax:  (216) 831-5579
  11. NOTE ** 
  12. NOTE ** Carlon single channel, two-channel, and multi-channel surface raceway is designed for power, low voltage, data and communication wiring in a one, two, or three channel configuration.
  13. NOTE ** 
  14. NOTE ** SECTION 16132 - SURFACE NONMETALLIC RACEWAYS, Copyright 1998, The Architect's Catalog, Inc.
  15.  
  16. PART 1    GENERAL
  17.  
  18. 1.1    SECTION INCLUDES
  19.  
  20.     A.    Surface raceway including base, cover, boxes, fittings, etc.
  21.  
  22. 1.2    RELATED SECTIONS
  23. NOTE ** Delete any sections below not relevant to this project;  add others as required.
  24.  
  25.     A.    Section 16123 - Building Wire and Cable.
  26.  
  27.     B.    Section 16140 - Wiring Devices.
  28.  
  29. 1.3    REFERENCES
  30.  
  31.     A.    NECA (INST) - NECA Standard of Installation; National Electrical Contractors Association.
  32.  
  33.     B.    NEMA WD 6 - Wiring Devices - Dimensional Requirements; National Electrical Manufacturers Association.
  34.  
  35.     C.    NFPA 70 - National Electrical Code.
  36.  
  37. 1.4    SUBMITTALS
  38.  
  39.     A.    Submit under provisions of Section 01300.
  40.  
  41.     B.    Product Data:  Provide standard details and installation instructions.
  42.  
  43.  
  44. PART 2    PRODUCTS
  45.  
  46. 2.1    MANUFACTURER
  47.  
  48.     A.    Provide products offered by Carlon, 25701 Science Park Drive, Cleveland, Ohio  44122.  ASD. Tel: outside of Ohio; (800) 321-1970, within Ohio; (216) 464-3400, TDD: (216) 831-5918.  Fax: (216) 831-5579.
  49.         1.    Substitutions will not be acceptable.
  50.  
  51. 2.2    MATERIALS
  52.  
  53.     A.    White polyvinyl chloride (PVC) meeting UL 94 V-O requirements.
  54.  
  55.     B.    Suitable for field painting.
  56.  
  57. 2.3    PRODUCTS
  58.  
  59.     A.    Provide "Single-Channel and Multi-Channel Surface Raceway System".
  60.  
  61.     B.    Provide protection for power, low voltage, and data and communication wiring in a 1, 2, or 3 channel configuration.
  62.  
  63.     C.    Recognized by NEC Article 352-B for Surface Nonmetallic Raceway.
  64.  
  65.     D.    UL listed for electrical wiring up to 300 volts;  comply with UL-5A.  UL File numbers:  "MC Standard Raceway", UL E140972, "MC Boxes and Fittings", UL E140971.
  66.  
  67.     E.    Finished surfaces are protected with blue plastic film.
  68.  
  69.     F.    Provide all fittings required to form a complete, integrated surface raceway system.
  70.  
  71.     G.    Receptacles and other devices:  Specified elsewhere in Division 16.
  72.  
  73. 2.4    FABRICATION
  74.  
  75.     A.    Fabricate raceway from precision extruded polyvinyl chloride plastic.
  76.  
  77.     B.    Fabricate raceway with the following cross sectional areas:
  78.         1.    Center channel:  5.4 square inches.
  79.         2.    Chamfered:       1.4 square inches.
  80.         3.    Square:          2.4 square inches.
  81.         4.    Extension:       5.3 square inches.
  82.         5.    Cove, center:    2.2 square inches.
  83.         6.    Cove, edges:     0.6 square inch.
  84.         7.    Series 10:       0.239 square inch.
  85.         8.    Series 30:       0.716 square inch.
  86.         9.    Series 80:       0.867 square inch.
  87.         10.    Series 90:       1.183 square inches.
  88.         11.    Premier:         6.287 square inches.
  89.  
  90.     C.    Raceway Covers:
  91.         1.    "MC Cove":  Single base and a single removable snap fit cover.
  92.  
  93.         2.    "MC Base":  Single base and four removable snap-on covers.
  94.  
  95.         3.    "Premier":  Single base and single removable snap-on covers.
  96.  
  97.     D.    Boxes:
  98.         1.    Device yoke:  Snap into raceway and allow installation of NEMA standard devices.
  99.         2.    Device back box:  Snap into device yoke to allow separation of wiring system.
  100.         3.    Transition lid adapter:  Location posts to allow proper alignment of device yoke to achieve additional depth by attaching box lid with screws.
  101.  
  102.     E.    Premier Multi-Channel Fittings:
  103.         1.    Internal and external elbow:  Molded fitting cover which snaps onto main base.
  104.         2.    Flat elbows and flat tees:  Molded fitting cover which snaps onto main base.
  105.         3.    Cable retainers:  Snaps into main base.
  106.         4.    Adapters:  Allows transition to "Single Channel (SC) Raceway Systems."
  107.         5.    Dividers:  Allows one-channel system to be divided into two-through-four channels.
  108.  
  109.     F.    Prestige Multi-Channel Fittings:
  110.         1.    Internal and external elbow:  Molded-in coupling for connection into main base.
  111.         2.    Flat elbows and flat tee: Attaches to main base by means of slide-in coupling.
  112.         3.    Cable retainers:  Snaps into main base.
  113.         4.    Adapters:  Allows transition to "Single Channel (SC) Raceway Systems."
  114.         5.    Crossover bridge:  Allow capability of routing cabling and wiring between outer channels.
  115.  
  116. 2.5    MULTI-CHANNEL RACEWAY
  117. NOTE ** Delete any of the following series that are not required on the project.  Indicate extent of raceway on the drawings.
  118.  
  119.     A.    Provide the following, where indicated on the drawings:
  120.         1.    "Series 120" raceway.
  121.         2.    "Series 130" raceway.
  122.         3.    "Series 140" raceway.
  123.         4.    "Series 160" raceway.
  124.         5.    "Series 170" raceway.
  125.         6.    "Series 190" raceway.
  126.         7.    "Series 500" raceway (Premier).
  127.         8.    "Series 10" (single channel).
  128.         9.    "Series 30" (single channel).
  129.         10.    "Series 80" (single channel).
  130.         11.    "Series 90" (single channel).
  131.  
  132.  
  133. PART 3    EXECUTION
  134.  
  135. 3.1    EXAMINATION
  136.  
  137.     A.    Verify that dimensions are correct and substrates are in proper condition to receive raceway.  Do not proceed with installation until unsatisfactory conditions have been corrected.
  138.  
  139. 3.2    INSTALLATION
  140.  
  141.     A.    Install in accordance with the manufacturer's instructions, NFPA 70, and NECA standard.
  142.  
  143.     B.    Install cover seals between adjoining sections of covers for a neat, aesthetic appearance.
  144.  
  145.     C.    Install base, cover, boxes, fittings, accessories, etc., as necessary for a complete system.
  146.  
  147. 3.3    ADJUST AND CLEAN
  148.  
  149.     A.    Remove temporary plastic protective film after completion of work by other trades, and adjust prior to substantial completion of the project.
  150.  
  151.  
  152.     END OF SECTION
  153. ??
  154.  
  155.  
  156.  
  157.  
  158.  
  159.  
  160.  
  161.  
  162.  
  163.     16132-1
  164.  
  165.  
  166.